Selection Criteria for Emergency Relief on Genset Tanks
A diesel generator subbase tank fits under the generator. The emergency vent shares the tank top with various fill, alarm, gauging, and overfill prevention components. The tank size and layout affect which emergency vent fits the tank and leaves enough room for maintenance.
Normal Venting and Emergency Venting Are Different Things
Normal venting handles the routine pressure and vacuum changes of tank operation. Emergency venting handles an abnormal event, such as when an aboveground tank is exposed to an external fire.
An emergency pressure relief vent opens at a set pressure and releases abnormal overpressure before it can rupture the tank. For tanks built to UL 142, the standard for steel aboveground tanks, each primary tank must have provision for both normal venting and emergency relief, so one function cannot stand in for the other.
The Code Basis for Emergency Pressure Relief
The International Fire Code, in section 5704.2.7.4, requires stationary aboveground tanks to have additional venting that relieves excessive internal pressure caused by fire exposure. NFPA 30, the Flammable and Combustible Liquids Code, covers relief for fire exposure in section 22.7. The NFPA 30 explains that this venting prevents tank rupture from an external fire, and sets a minimum relief capacity the vent has to meet.
These provisions apply to aboveground tanks generally. A generator tank’s requirements are specific to its construction, listing, capacity, type of fuel stored, and the Authority Having Jurisdiction (AHJ).
Generator Tank Conditions That Affect Emergency Vent Selection
- Double-wall and subbase tanks. UL 142 also requires emergency relief for the interstitial space of a secondary containment tank, with its own opening at the top of the secondary containment. That can mean two relief devices on one tank.
- Space on the tank top. Room for fittings and components is often limited on a genset tank. Clay & Bailey’s instructions state that there should be nothing around or above the emergency vent, so the area must be free from any obstruction for proper relief.
- Connections. The tank’s openings determine the connection size, the thread type, or the flange pattern the vent must match.
- Neighboring components. Components must not interfere with the normal vent or the emergency vent.
Relief Capacity and Listing Requirements
Relief capacity comes first. An emergency pressure relief vent must meet the required tank relief venting capacity. The UL/ULC 2583 requires each emergency vent to list its opening pressure and relief flow capacity at 2.5 psi on the device body or a permanent nameplate. Specifiers can compare the nameplate data directly against the tank’s requirement.
The UL/ULC 2583, Fuel Tank Accessories for Flammable and Combustible Liquids, contains functional testing requirements for these devices. Clay & Bailey’s emergency vent family is covered by UL File MH25085, and the company describes individual models as UL/ULC Listed where noted on each product page.
To check sizes, relief flow rates, and listings side by side, review Clay & Bailey’s emergency vent range and each model’s spec sheet before you finalize the tank drawing and make a selection. Or call (800) 821-6583 to discuss your specific application in person.
Thread and Flange Connections: 366, 367, and 370
Clay & Bailey’s aluminum high-flow vents come in two thread versions. The 366 high-flow vent has a female thread, and the 367 high-flow vent has a male thread. Both are spring loaded and fitted with a Buna-N O-ring and optional screen, and the spec sheets offer sizes from 3″ to 8″. 370 Flanged emergency vents are available in sizes from 6” to 10”. Clay & Bailey includes both in its Genset category.
Construction and fuel also determine the proper thread and flange connection. The high-flow spec sheets describe all-aluminum construction as lighter and rust-free, while the 365 and 369 use heavy-duty cast-iron tops. Clay & Bailey’s March 2026 instructions state that the emergency vent they cover is typically used with diesel and gasoline fuels, so diesel generator service falls within its stated use.
Where the tank has a flanged opening, the 370 flanged, bolt-on vent removes the need for a pipe nipple and uses a flange hole pattern conforming to the ANSI B16.5 footprint.
Slimline Designs and the 365 and 369 Models
Clay & Bailey describes its slimline style as ideal for limited space applications. The 366 slimline has a 4″ female NPT thread, and its spec sheet gives an opening pressure set below 0.5 psig. The 367 slimline is the male-thread version, offered in 4″, 5″, and 6″ sizes. Choosing between them follows the same rule as the high-flow emergency vents: match the slimline emergency pressure relief vent to the thread size of the tank opening and required relief capacity.
The 365 and 369, which Clay & Bailey describes as UL/ULC Listed, are both emergency vent options. The 365 has a 3″ male NPT connection and a cast-iron top on a cast-iron or aluminum base. The 369 has a male thread in 4″, 6″, and 8″ sizes and a heavy cast-iron “mushroom” top that acts as a weather deflector. A tank that needs more capacity than the 365 provides can use the 369’s larger sizes or the high-flow and flanged models.
Specifying the Right Emergency Vent With Clay & Bailey
Clay & Bailey’s tank equipment is American-made in Kansas City, where the company has operated since 1913. Choosing an emergency vent for fuel tank applications on a generator package means matching relief capacity, opening pressure, connection, tank-top space, and listing. Clay & Bailey can help identify the right model for your tank. Call (800) 821-6583 to discuss your application.